H07V-K IEC 227 HD 21.3 S3

  BACK

APPLICATION PLACE TECHNICAL DATA
In moving places and used for instrument
cabling and equipment connection, in the
pipe, under or on the plaster.
Maximum working temperature: 70°C
Short circuit temperature: 160°C
(Max for 5 Sec.)
Rated Voltage: Uo/U - 300/500V (H05V)
  Uo/U - 450/750V (H07V)

Test Voltage: 2 kV - 2.5 kV (AC)
Size and weights Electrical Specification
Type Nominal
Cross Section
Overal diameter
approx
Net weight
weight approx
Standart delivery lenght Type of
packing.coil
or drum size

Conductor DC
resistance at
20°C max.
Current Carrying capacity
In ground 20°Cmax. in air 30°C max.
  mm2 mm kg/km m cm ohm/km A A
H05V-K 0.50 2.2 9 100 Coil 39.0 - 12
H05V-K 0.75 2.5 15 100 Coil 26.0 - 15
H05V-K 1 2.6 17 100 Coil 19.5 11 19
H07V-K 1.5 3.0 20 100 Coil 13.3 15 24
H07V-K 2.5 3.8 35 100 Coil 7.98 20 32
H07V-K 4 4.5 50 100 Coil 4.95 25 42
H07V-K 6 5.0 75 100 Coil 3.3 33 54
H07V-K 10 6.5 125 100 Coil 1.91 45 73
H07V-K 16 7.8 180 100 Coil 1.21 61 98
H07V-K 25 10.0 280 100 Coil 0.780 83 129
H07V-K 35 11.0 380 100 Coil 0.554 103 158
H07V-K 50 13.5 550 1000 101 0.386 132 198
H07V-K 70 15.5 760 1000 101 0.272 165 245
H07V-K 95 18.0 970 1000 121 0.206 197 292
H07V-K 120 20.0 1230 1000 121 0.161 235 344
H07V-K 150 22.0 1490 1000 141 0.129 - 391
H07V-K 185 24.0 1840 1000 141 0.106 - 448
H07V-K 240 28.0 2400 1000 161 0.0801 - 528
 