N2XFGbY  IEC 60502 -  1  0,6 / 1kV

  BACK

APPLICATION PLACE TECHNICAL DATA
These cables are used in the place where
has hard mechanical conditions,
underground installation, in power and
switching stations.If it is specially produced.
it can be used in freshwater and seawater.

Maximum working temperature: 90°C
Short circuit temperature: 250°C
(Max for 5 Sec.)
Rated Voltage: Uo/U - 0,6 / 1 kV
Test Voltage : 3,5 kV ( AC )
Bending Radius : 12xD
Size and Weights Electrical Specification
Nominal cross section Overall diameter approx. Net weight approx. Standard delivery lenght Type of packing, coil or drum size Conductor DC resistance at 20°C max. Current carrying capacity
In ground 20°C max. In air 30°C max.
mm* mm kg/km m cm ohm/km A A
3x16 23.0 1230 1000 141 1.15 111 96
3x25 26.0 1680 1000 141 0.727 143 130
3x35 29.0 2110 1000 161 0.524 173 160
3x50 31.0 2540 1000 161 0.387 205 195
3x70 36.0 3450 1000 181 0.268 252 247
3x95 40.0 4420 1000 221 0.193 303 305
3x120 44.0 5350 500 161 0.153 346 355
3x150 48.0 6470 500 181 0.124 390 407
3x185 53.0 7860 500 221 0.0991 441 469
3x240 59.0 10110 500 221 0.0754 511 551
3x300 65.0 12320 250 201 0.0601 580 638
3x400 73.0 15390 250 221 0.0470 663 746
4x16 24.0 1430 1000 141 1.15 111 96
4x25 29.0 2020 1000 161 0.727 143 130
4x35 32.0 2530 1000 161 0.524 173 160
4x50 34.0 3080 1000 161 0.387 205 195
4x70 40.0 4240 1000 221 0.268 252 247
4x95 44.0 5430 500 161 0.193 303 305
4x120 48.0 6660 500 181 0.153 346 355
4x150 53.0 8100 500 221 0.124 390 407
4x185 58.0 9750 500 221 0.0991 441 469
4x240 66.0 12720 250 201 0.0754 511 551
4x300 72.0 15360 250 221 0.0601 580 638
4x400 80.0 19330 250 221 0.0470 663 746

         N2XFGbY  IEC 60502 -  1  0,6 / 1kV
APPLICATION PLACE TECHNICAL DATA
These cables are used in the place where
has hard mechanical conditions,
underground installation, in power and
switching stations.If it is specially produced.
it can be used in freshwater and seawater.

Maximum working temperature: 90°C
Short circuit temperature: 250°C
(Max for 5 Sec.)
Rated Voltage: Uo/U - 0,6 / 1 kV
Test Voltage : 3,5 kV ( AC )
Bending Radius : 12 x D
Size and Weights Electrical Specification
Nominal cross section Overall diameter approx. Net weight approx. Standard delivery lenght Type of packing, coil or drum size Conductor DC resistance at 20°C max. Current carrying capacity
In ground 20°C max. In air 30°C max.
mm2 mm kg/km m cm ohm/km A A
3x25+16 28.0 1860 1000 141 0.727 143 130
3x35+16 30.0 2280 1000 141 0.524 173 160
3x50+25 33.0 2830 1000 161 0.387 205 195
3x70+35 37.0 3810 1000 201 0.268 252 247
3x95 +50 42.0 4900 1000 221 0.193 303 305
3x120 + 70 46.0 6090 500 161 0.153 346 355
3x150 + 70 50.0 7140 500 201 0.124 390 407
3x185+95 55.0 8790 500 221 0.0991 441 469
3x240+120 61.0 11240 250 201 0.0754 511 551
3x300+150 67.0 13720 250 201 0.0601 580 638
3x400 + 185 75.0 17270 250 743 744 745 746